AT-DC2552XS
L2 Data Center Switch
Installation Guide
Przeglądanie stron 0
1 2 3 4 5 6 ... 83 84

Podsumowanie treści

Strona 1 - Installation Guide

613-001760 Rev. AAT-DC2552XSL2 Data Center SwitchInstallation Guide

Strona 2

Tables10

Strona 3 - Industry Canada

11PrefaceThis guide contains instructions on how to install the AT-DC2552XS L2 Data Center Switch and the associated power supply and fan modules on a

Strona 4 - Translated Safety Statements

Preface12Document ConventionsThis document uses the following conventions:NoteNotes provide additional information.CautionCautions inform you that per

Strona 5 - Contents

Stack Installation Guide for AT-2552XS L2 Data Center Switch13Contacting Allied TelesisIf you need assistance with this product, you may contact Allie

Strona 6

Preface14

Strona 7

15Chapter 1OverviewThis chapter contains the following sections: “AT-DC2552XS Features” on page 16 “LEDs” on page 23 “Console Port” on page 29 “AT

Strona 8

Chapter 1: Overview16AT-DC2552XS FeaturesThe AT-DC2552XS L2 Data Center Switch has a high-density switching fabric (1280 Gbps) in a compact 1 RU chass

Strona 9

Stack Installation Guide for AT-2552XS L2 Data Center Switch17Installation OptionsThe AT-DC2552XS L2 Data Center Switch is designed to be installed in

Strona 10

Chapter 1: Overview18Optional QSFP+ TransceiversThe following QSFP+ transceivers direct attach cable assemblies have been approved by Allied Telesis a

Strona 11

Stack Installation Guide for AT-2552XS L2 Data Center Switch19AT-DC2552XSPhysicalDescriptionThe AT-DC2552XS L2 Data Center Switch physical description

Strona 12 - Document Conventions

Copyright © 2013 Allied Telesis, Inc.All rights reserved. No part of this publication may be reproduced without prior written permission from Allied T

Strona 13 - Contacting Allied Telesis

Chapter 1: Overview20NoteThe AT-PWR06 power supply module is sold and packaged separately from the AT-DC2552XS L2 Data Center Switch. The fan module

Strona 14

Stack Installation Guide for AT-2552XS L2 Data Center Switch21WarningKeep the exhaust air vents clear of any obstructions to insure proper cooling of

Strona 15 - Overview

Chapter 1: Overview22“Power/Fault LED” on page 25 for the functional description. Console Port - The console port is a standard RS-232 interface usin

Strona 16 - AT-DC2552XS Features

Stack Installation Guide for AT-2552XS L2 Data Center Switch23LEDsHere are the descriptions of the switch’s LEDs.SFP+ Slot LED Each SFP+ slot has one

Strona 17 - Optional SFP+ Transceivers

Chapter 1: Overview24QSFP+ Slot LEDs Each QSFP+ port has one link/activity LED labeled LINK/ACT. These LEDs are shown in Figure 4.Figure 4. QSFP+ LEDs

Strona 18 - Optional QSFP+ Transceivers

Stack Installation Guide for AT-2552XS L2 Data Center Switch25Power/Fault LED The Power/Fault LED are shown in Figure 5.Figure 5. Power/Fault LEDsThe

Strona 19 - Description

Chapter 1: Overview26NET MGMTLEDThe NET MGMT LED are shown in Figure 6.Figure 6. NET MGMT LEDsThe NET MGMT LEDs are described in Table 5.LINKLEDACTLED

Strona 20

Stack Installation Guide for AT-2552XS L2 Data Center Switch27FAN Status LEDs The fan status LEDs are shown in Figure 7.Figure 7. FAN Status LEDsThe f

Strona 21

Chapter 1: Overview28AC Power LED Each AT-PWR06 power supply module has a AC power (AC OK) LED. This LED is shown in Figure 8.Figure 8. AC Power LEDTh

Strona 22

Stack Installation Guide for AT-2552XS L2 Data Center Switch29Console PortThe Console port is used to locally configure the features and parameter set

Strona 23

3Electrical Safety and Emissions StandardsThis product meets the following standards.RFI Emissions FCC Class A, EN55022 Class A, CISPR 22 Class A, VCC

Strona 24 - Chapter 1: Overview

Chapter 1: Overview30AT-PWR06 Power Supply ModuleThe AT-DC2552XS L2 Data Center Switch is powered by one AT-PWR06 power supply module. A second AT-PWR

Strona 25

Stack Installation Guide for AT-2552XS L2 Data Center Switch31The components of the AT-PWR06 power supply module (refer to Figure 9 on page 30) are as

Strona 26 - NET MGMT

Chapter 1: Overview32AT-FAN06 Fan ModuleInstallation of two AT-FAN06 fan modules are required in the AT-DC2552XS. Each AT-FAN06 fan module is equipped

Strona 27

33Chapter 2Beginning the InstallationThe chapter contains the following sections: “Installation Overview” on page 34 “Reviewing Safety Precautions”

Strona 28

Chapter 2: Beginning the Installation34Installation OverviewTable 8 lists the installation procedures for the AT-DC2552XS L2 Data Center Switch. The p

Strona 29 - Console Port

Stack Installation Guide for AT-2552XS L2 Data Center Switch35Reviewing Safety PrecautionsPlease review the following safety precautions before you be

Strona 30 - AT-PWR06 Power Supply Module

Chapter 2: Beginning the Installation36WarningClass I Equipment. This equipment must be earthed. The power plug must be connected to a properly wired

Strona 31

Stack Installation Guide for AT-2552XS L2 Data Center Switch37CautionRisk of explosion if battery is replaced by an incorrect type. Replace only with

Strona 32 - AT-FAN06 Fan Module

Chapter 2: Beginning the Installation38WarningReliable earthing of rack-mounted equipment should be maintained. Particular attention should be given t

Strona 33 - Beginning the Installation

Stack Installation Guide for AT-2552XS L2 Data Center Switch39Planning the InstallationThe AT-DC2552XS L2 Data Center Switch can be installed on a des

Strona 34 - Installation Overview

4Translated Safety StatementsImportant: The  indicates that translations of the safety statement are available in the PDF document “Translated Safety

Strona 35 - Reviewing Safety Precautions

Chapter 2: Beginning the Installation40Unpacking the SwitchRefer to the following figures in this section to verify the contents of the shipping conta

Strona 36

Stack Installation Guide for AT-2552XS L2 Data Center Switch41AT-PWR06Power SupplyThe contents of the AT-PWR06 power supply module shipping box are li

Strona 37

Chapter 2: Beginning the Installation42AT-FAN06 FanModuleThe contents of the AT-FAN06 fan module shipping box are listed in Figure 12.Figure 13. Conte

Strona 38

43Chapter 3Installing the Switch and ModulesYou may install the AT-DC2552XS Switch on a desktop or in a standard 19 inch equipment rack. In addition,

Strona 39 - Planning the Installation

Chapter 3: Installing the Switch and Modules44Installing the Switch on a DesktopTo install the switch on a desktop, perform the following procedure:No

Strona 40 - Unpacking the Switch

Stack Installation Guide for AT-2552XS L2 Data Center Switch45Installing the Switch in an Equipment RackNoteTo install the switch on a desktop, refer

Strona 41 - Power Supply

Chapter 3: Installing the Switch and Modules46This procedure requires the following items: Eight bracket screws (included with the switch) Two equip

Strona 42 - AT-FAN06 Fan

Stack Installation Guide for AT-2552XS L2 Data Center Switch472. Have another person hold the switch in the equipment rack while you secure it using s

Strona 43 - Chapter 3

Chapter 3: Installing the Switch and Modules48Installing and Replacing AT-PWR06 Power Supply ModuleThe AT-PWR06 power supply module may be installed i

Strona 44

Stack Installation Guide for AT-2552XS L2 Data Center Switch49CautionThe PSU blank cover should be installed if an AT-PWR06 power sup-ply module is no

Strona 45

5Preface...

Strona 46

Chapter 3: Installing the Switch and Modules505. Tighten the captive screws to fasten of the power supply module to the chassis. See Figure 20.Figure

Strona 47

Stack Installation Guide for AT-2552XS L2 Data Center Switch51NoteIf a new AT-PWR06 power supply module is not available to replace the module you are

Strona 48 - Supply Module

Chapter 3: Installing the Switch and Modules52Installing and Replacing AT-FAN06 Fan ModuleThe following procedures are included in this section: “Ins

Strona 49

Stack Installation Guide for AT-2552XS L2 Data Center Switch534. Tighten the captive screws to fasten the fan module to the chassis. See Figure 23.Fig

Strona 50 - Replacing Power

Chapter 3: Installing the Switch and Modules54Replacing FanModuleThe AT-FAN06 fan module is hot swappable within the chassis. The power to the chassis

Strona 51 - Supply Blank

55Chapter 4Installing the SFP+ and QSFP+ Transceivers and CablesThe list of approved SFP+ and QSFP+ transceivers and direct connect cables that may be

Strona 52 - Installing Fan

Chapter 4: Installing the SFP+ and QSFP+ Transceivers and Cables56Installing SFP+ Transceivers and CablesGeneralGuidelinesReview the following guideli

Strona 53

Stack Installation Guide for AT-2552XS L2 Data Center Switch57Installing SFP+TransceiverPerform the following procedure to install a SFP+ transceiver:

Strona 54 - Replacing Fan

Chapter 4: Installing the SFP+ and QSFP+ Transceivers and Cables58Figure 26. Installing a SFP+ TransceiverNoteIf you are ready to attach the fiber opt

Strona 55 - Transceivers and Cables

Stack Installation Guide for AT-2552XS L2 Data Center Switch597. Refer to Table 9 on page 56 for the recommended fiber optic cable. Insert the cable t

Strona 56 - Guidelines

Contents6Chapter 6: Managing the Switch ...

Strona 57 - Transceiver

Chapter 4: Installing the SFP+ and QSFP+ Transceivers and Cables602. Remove the SFP+ direct attach cable from its shipping container and store the pac

Strona 58

Stack Installation Guide for AT-2552XS L2 Data Center Switch61Installing QSFP+ Transceivers and CablesReview the following guidelines before installin

Strona 59 - Direct Attach

Chapter 4: Installing the SFP+ and QSFP+ Transceivers and Cables62Figure 31. Removing QSFP+ Slot Dust Cover3. If you are installing the transceiver in

Strona 60

Stack Installation Guide for AT-2552XS L2 Data Center Switch63Figure 33. Removing QSFP+ Dust Cover7. Insert the fiber optic cable to the port on the t

Strona 61 - Installing a

Chapter 4: Installing the SFP+ and QSFP+ Transceivers and Cables64Figure 35. Removing QSFP+ Slot Dust Cover3. If you are installing the QSFP+ MTHTP ca

Strona 62

65Chapter 5Powering the SwitchThe procedures in this chapter are listed here: “Powering On the Switch” on page 66 “Turn Off the switch” on page 68

Strona 63 - QSFP+ MTHTP

Chapter 5: Powering the Switch66Powering On the SwitchThe power turns on automatically when you connect the power cable to one or both of the AT-PWR06

Strona 64

Stack Installation Guide for AT-2552XS L2 Data Center Switch676. The next step in the installation process is to access the AT-DC2552XS management int

Strona 65 - Powering the Switch

Chapter 5: Powering the Switch68Turn Off the switchTo turn off the AC power to the switch, perform the following procedure.WarningPower cord is used a

Strona 66 - Powering On the Switch

69Chapter 6Managing the SwitchYou may manage an AT-DC2552XS L2 Data Center Switch with these methods and tools: Local management via Telnet client R

Strona 67 - Console port

7Figure 1: AT-DC2552XS Front Panel View ...

Strona 68 - Turn Off the switch

Chapter 6: Managing the Switch70Local ManagementYou can manage the AT-DC2552XS switch locally through the Console port (USB connector) the rear panel

Strona 69 - Managing the Switch

Stack Installation Guide for AT-2552XS L2 Data Center Switch71 Stop bits: 1 Flow control: None NoteThe port settings are for a DEC VT100 or ANSI ter

Strona 70 - Local Management

Chapter 6: Managing the Switch72Remote Network Management You can manage the AT-DC2552XS switch remotely through any of the Ethernet ports (1 through

Strona 71 -  Flow control: None

Stack Installation Guide for AT-2552XS L2 Data Center Switch73Figure 38. Connecting the Twisted Pair Cable into the NET MGMT port3. With the AT-DC2552

Strona 72 - Remote Network Management

Chapter 6: Managing the Switch74

Strona 73

75Chapter 7TroubleshootingThis chapter contains suggestions on how to troubleshoot the switch if a problem occurs.NoteFor further assistance, please c

Strona 74

Chapter 7: Troubleshooting76 Verify that the operating specifications of the fiber optic ports on the SFP+ transceiver and the remote network device

Strona 75 - Troubleshooting

Stack Installation Guide for AT-2552XS L2 Data Center Switch77 If the remote network device is a managed device, use its management firmware to deter

Strona 76

Chapter 7: Troubleshooting78

Strona 77

79Appendix ATechnical SpecificationsThis appendix contains the technical specifications for the AT-DC2552XS L2 Data Center Switch.Physical Specificati

Strona 79 - Technical Specifications

Appendix A: Technical Specifications80Power SpecificationsAT-PWR06 Input SpecificationsCertificationsQuality and ReliabilityTable 14. AT-PWR06 Input

Strona 80 - Quality and Reliability

Stack Installation Guide for AT-2552XS L2 Data Center Switch81RJ-45 Twisted Pair Port PinoutsFigure 39 illustrates the pin layout of an RJ-45 connecto

Strona 81

Appendix A: Technical Specifications82Table 18 lists the pin signals when a port operating at 1000 Mbps.Table 18. Pin Signals - 1000 MbpsPinout Pair

Strona 82

Stack Installation Guide for AT-2552XS L2 Data Center Switch83

Strona 83

Appendix A: Technical Specifications84

Strona 84